Operation
Configuring Automatic Start Delay
You can configure a load segment to turn on automatically after the utility power returns, if it was shut
down by:
S The button
S An external command with auto-restart option
S Battery under voltage state
S Automatic on battery shutdown command
You can specify the restart delay time for each load segment: select zero seconds (0s is the default) to
restart immediately, select 1–32767 seconds to delay for the specified time, or select Off.
To set the restart delay times for each load segment:
1 Press the button for longer than one second to go to the main menu selection and scroll down to
the Settings menu using the
button.
2 Press the button to enter the Settings menu.
3 Use the button to scroll to the Automatic Start Delay option and press the button.
The current setting for the option flashes when selected.
4 Set the restart delay for one load segment using the and buttons.
5 Press the button to confirm.
6 Set the restart delay for the other load segment if applicable.
7 Press the button to confirm.
NOTE:
Load segment On/Off commands issued through the Control menu override the user settings for load
segments.
NOTE: There is an additional built-in one-second delay between closing load segment 1 and 2 when an On
command is issued for both segments at the same time.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Dell 5600R OL HV-US 5600W and is the answer not in the manual?

Dell 5600R OL HV-US 5600W Specifications

General IconGeneral
BrandDell
Model5600R OL HV-US 5600W
CategoryUPS
LanguageEnglish

Related product manuals