- 3 -
Storage temperature
-20
o
C ~ +65
o
C
Relative humidity 35% ~ 80% (non-condensing)
Altitude 2,000m or less
Installation environment Installation Category 33, Pollution Degree 2. Conforming to EN61010-1
Panel protection level IP65
Parameters List
1. Operation Mode: Perform per the settings of related control parameters
LED Display Explanation Default
RUN/STOP: Control setting begins. Run (
) or Stop ( ) mode on the SV display.
RUN
ALARM1 HIGH: Upper-limit alarm 1
4.0
o
C
ALARM1 LOW: Lower-limit alarm 1
4.0
o
C
ALARM2 HIGH: Upper-limit alarm 2
4.0
o
C
ALARM2 LOW: Lower-limit alarm 2
4.0
o
C
Setting lock: Lock 1 (
), Lock 2 ( ) or OFF ( ) on the SV display. Lock 1 mode can lock all
settings and Lock 2 mode only can lock others than SV value. When OFF mode is selected, the Lock
function will be OFF. If you press
and key simultaneously, the “Lock” status can be released and
the controller will be back to the previous display.
OFF
OUT: Output value display and output value adjustment in manual tuning control (This function is not
available in ON/OFF control or Auto-tuning setting)
0
CT: In case of using an external current transformer (CT), the controller displays the current value being
measured by CT, if the control output is ON
Read only
2. Regulation Mode: Set the control parameters
LED Display Explanation Default
AT: Auto-tuning setting. When AT key is set to ON (
), the execution of the PID auto-tuning function is
automatically started. (PID control)
OFF
P: Proportional Band (PID control) 47.6
I: Integral Time (PID control) 260
D: Derivative Time (PID control) 41
PdoF: Offset output when P or PD control function is ON. (PID control and Ki=0) 0
ioF: Default value of integral volume when PID control function is ON and integral time constant is not equal
to 0(zero). AT can automatically set this parameter. (PID control and Ki0)
0
HTS: Set Heating hysteresis when ON/OFF control function is ON. 0
CTS: Set Cooling hysteresis when ON/OFF control function is ON. 0
HTPD: PID heating control cycle setting (PID control)
CLPD: PID cooling control cycle setting (PID control)
Output
Selection:
V: 4 sec.
R: 20 sec.
TPOF: Regulate temperature deviation value 0
CRHI: Regulate 20mA output deviation value (1unit = 0.1mA) 0
CRLO: Regulate 4mA output deviation value (1unit = 0.1mA) 0
3. Initial Setting Mode: Initial settings of the controller and communication parameters
LED Display Explanation Default
INPUT: Select input temperature sensor type
(Please refer to the contents of the “Temperature Sensor Type and Temperature Range” for detail)
PT2
UNIT: Temperature display unit,
o
C ( ) and
o
F ( )
o
C
T-HIGH: Upper limit for temperature range 500.0