Temperature Sensor Type & Temperature Range
Input temperature sensor type Register value LED display Temperature range
Platinum resistance (Pt100) type 3 15
0.0 ~ 100.0
o
C
Platinum resistance (Pt100) type 2 14
-20.0 ~ 500.0
o
C
Platinum resistance (Pt100) type 1 13
-200 ~ 600
o
C
Platinum resistance (JPt100) type 2 12
0.0 ~ 100.0
o
C
Platinum resistance (JPt100) type 1 11
-20.0 ~ 400.0
o
C
Copper resistorCu50type2
20
-50.0 ~ 150.0°C
Copper resistorCu50type1
19
-50 ~ 150°C
Thermocouple (TC) B type 10
100 ~ 1,800
o
C
Thermocouple (TC) S type 9
0 ~ 1,700
o
C
Thermocouple (TC) R type 8
0 ~ 1,700
o
C
Thermocouple (TC) N type 7
-200 ~ 1,300
o
C
Thermocouple (TC) E type 6
0 ~ 600
o
C
Thermocouple (TC) T type 2 5
-20.0 ~ 400.0
o
C
Thermocouple (TC) T type 1 4
-200 ~ 400
o
C
Thermocouple (TC) J type 2 3
-20.0 ~ 400.0
o
C
Thermocouple (TC) J type 1 2
-100 ~ 850
o
C
Thermocouple (TC) K type 2 1
-20.0 ~ 500.0
o
C
Thermocouple (TC) K type 1 0
-200 ~ 1300
o
C
Thermocouple (TC) L type 16
-200 ~ 850
o
C
Thermocouple (TC) U type 17
-200 ~ 500
o
C
Thermocouple (TC) Txk type 18
-200 ~ 800
o
C
Input Error Indication
Set value
Temperature sensor not
connected
Measured temperature value exceeds temperature
range
Unknown input
PV
SV
Alarm Outputs
There are up to two groups of alarm outputs and each group allows 13 alarm types in the initial setting mode. The alarm output is activated
whenever the process temperature value (PV) is getting higher or lower than the set point of alarm limit.
Set value Alarm type Alarm output operation
0 Alarm function disabled
Output OFF
1
Deviation upper- and lower-limit:
This alarm output operates when PV value is higher than the setting value SV + (AL-H) or
lower than the setting value SV - (AL-L).
ON
OFF
SV-(AL-L)
SV
SV+(AL-H)
2
Deviation upper-limit:
This alarm output operates when PV value is higher than the setting value SV + (AL-H).
ON
OFF
SV
SV+(AL-H)
3
Deviation lower-limit:
This alarm output operates when PV value is lower than the setting value SV- (AL-L).
ON
OFF
SV
SV-(AL-L)