Chapter 8 Optional Cards MS300 (IP66 / NEMA 4X)
8-7
8-2 CMM-MOD01 -- Communication Extension Card, Modbus TCP
Product Profile
5(NET2)
5(NET1)
6
2
4
3
2
2
2
1
Features
1. Supports Modbus TCP protocol
2. MDI / MDI-X auto-detect
3. E-mail alarm
4. IP Filter firewall
Specifications
Network Interface
Interface RJ45 with Auto MDI / MDIX
Number of ports 1 Port
Transmission method IEEE 802.3, IEEE 802.3u
Transmission cable Category 5e shielding 100 M
Transmission speed 10/100 Mbps Auto-Detect
Network protocol
ICMP, IP, TCP, UDP, DHCP, SMTP,
Modbus TCP, Delta Configuration
Electrical Specification
Power supply voltage
5
V
DC
(supplied by AC motor drive)
Insulation voltage
500
V
DC
Power consumption
0.8 W
Weight
25 g
Environment
Noise immunity
ESD (IEC 61800-5-1, IEC 6100-4-2)
EFT (IEC 61800-5-1, IEC 6100-4-4)
Surge Test (IEC 61800-5-1, IEC 6100-4-5)
Conducted Susceptibility Test (IEC 61800-5-1, IEC 6100-4-6)
Wire: 0.25–0.5 mm
2
[24–20 AWG]
Stripping length: 7–8 mm
Torque: 2 kg-cm[1.7 Ib-in.][0.2 Nm]
1. Screw fixing hole
2. Positioning hole
3. AC motor drive
connection port
4. Communication port
5. Indicator
6. Ground terminal block

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta Compact Drive MS300 IP66/NEMA 4X Series and is the answer not in the manual?

Delta Compact Drive MS300 IP66/NEMA 4X Series Specifications

General IconGeneral
BrandDelta
ModelCompact Drive MS300 IP66/NEMA 4X Series
CategoryDC Drives
LanguageEnglish

Related product manuals