Chapter 8 Optional Cards MS300 (IP66 / NEMA 4X)
8-10
8-3 CMM-PD01 -- Communication Extension Card, PROFIBUS DP
Product Profile
2
4
3
2
2
2
1
5(NET2)
5(NET1)
6
Features
1. Supports PZD control data exchange.
2. Supports PKW polling AC motor drive parameters.
3. Supports user diagnosis function.
4. Auto-detects baud rates; supports maximum of 12 Mbps.
Specifications
PROFIBUS DP Connector
Interface DB9 connector
Transmission
method
High-speed RS-485
Transmission cable Shielded twisted pair cable
Electrical isolation
500
V
DC
Communication
Message type Cyclic data exchange
Module name CMM-PD01
GSD document DELA08DB.GSD
Product ID 08DB (hex)
Serial transmission
speed supported
(auto-detection)
9.6 kbps; 19.2 kbps; 93.75 kbps; 187.5 kbps; 500 kbps; 1.5 Mbps; 3 Mbps; 6 Mbps;
12 Mbps (bits per second)
Electrical Specification
Power supply
5
V
DC
(supplied by AC motor drive)
Insulation voltage
500
V
DC
Power consumption 1 W
Weight 28 g
Wire: 0.25–0.5 mm
2
[24–20 AWG]
Stripping length: 7–8 mm
Torque: 2 kg-cm[1.7 Ib-in.][0.2 Nm]
1. Screw fixing hole
2. Positioning hole
3. AC motor drive connection
port
4. Communication port
5. Indicator
6. Ground terminal block

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta Compact Drive MS300 IP66/NEMA 4X Series and is the answer not in the manual?

Delta Compact Drive MS300 IP66/NEMA 4X Series Specifications

General IconGeneral
BrandDelta
ModelCompact Drive MS300 IP66/NEMA 4X Series
CategoryDC Drives
LanguageEnglish

Related product manuals