Chapter 12 Description of Parameter Settings
ME300
12-1 Description of Parameter Settings
00 Drive Parameters
You can set this parameter during operation.
AC motor drive identity code
Default: Read only
Settings Read Only
AC motor drive rated current display
Default: Read only
Settings Read Only
Pr.00-00 displays the identity code of the AC motor drive. Use the following specification table to
check if Pr.00-01 setting is the rated current of the AC motor drive. Pr.00-01 corresponds to the
identity code of the motor.
The default is the rated current for heavy duty. Set Pr.00-16 to 0 to display the rated current for
normal duty.
Models 115V Models: One-Phase 230V Models: One-Phase
Frame A B C A/B B C
kW 0.1 0.2 0.4 0.75 0.1 0.2 0.4 0.75 1.5 2.2
HP 0.125 0.25 0.5 1 0.125 0.25 0.5 1 2 3
Identity Code 101 102 103 104 301 302 303 304 305 306
Rated Current for
Heavy Duty
0.8 1.6 2.5 4.8 0.8 1.6 2.8 4.8 7.5 11
Rated Current for
Normal Duty
1 1.8 2.7 5.5 1 1.8 3.2 5 8.5 12.5
Models 230V Models: Three-Phase
Frame A B C D E F
kW 0.1 0.2 0.4 0.75 1.5 2.2 3.7 / 4 5.5 7.5 11 15
HP 0.125 0.25 0.5 1 2 3 5 7.5 10 15 20
Identity Code 201 202 203 204 205 206 207 208 209 210 211
Rated Current for
Heavy Duty
0.8 1.6 2.8 4.8 7.5 11 17 25 33 49 65
Rated Current for
Normal Duty
1 1.8 3.2 5 8 12.5 19.5 27 36 51 69
Models 460V Models: Three-Phase
Frame A/B B C D E F
kW 0.4 0.75 1.5 2.2 3 3.7 / 4
5.5 7.5 11 15 18.5 22
HP 0.5 1 2 3 4 5 7.5 10 15 20 25 30
Identity Code 403 404 405 406 482 407 408 409 410 411 412 413
Rated Current for
Heavy Duty
1.5 2.7 4.2 5.5 7.3 9 13 17 25 32 38 45
Rated Current for
Normal Duty
1.8 3 4.6 6.5 8 10.5 15.7 20.5 28 36 41.5 49