Chapter 12 Description of Parameter Settings
ME300
12 Function Parameters
In this parameter group, ASR stands for Adjust Speed Regulator.
You can set this parameter during operation.
Set Point Deviation Level
D
efault: 0
Settings 0–100%
Detection Time of Set Point Deviation Level
D
efault: 10
Settings 1–9999 sec.
When the deviation is less than Pr.12-00 (in the range of PID set point to Pr.12.00 x PID set point)
for a time exceeding the setting of Pr.12-01, the AC motor drive decelerates to stop to be constant
pressure status (this deceleration time is the setting for Pr.01-15). The system is ready when the
deviation is within the range of PID set point to Pr.12-00 x PID set point during deceleration.
Example:
If the set point of constant pressure control of a pump is 4 kg, Pr.12-00 is set to 5%, and Pr.12-01
is set to 15 seconds, then the deviation is 0.2 kg (4 kg × 5%=0.2 kg). It means when the feedback
value is higher than 3.8 kg for a time exceeding 15 seconds, the AC motor drive decelerates to
stop (this deceleration time acts according to Pr.01-12). When the feedback value is less than 3.8
kg, the AC motor drive starts to run.
Offset Level of Liquid Leakage
D
efault: 0
Settings 0–50%
In the constant pressure status, when the liquid leakage is higher than Pr.12-02 x PID set point,
the AC motor drive starts to run.
It is used to prevent the drive from frequent run/stop operation due to liquid leakage.
Liquid Leakage Change Detection
Default: 0
Settings 0: Disable
0–100%
Time Setting for Liquid Leakage Change
D
efault: 0.5
Settings 0: Disable
0.1–10.0 sec.