Chapter 15 Safe Torque Off Function
ME300
15-8
15-6-5 STL2, Pr.06-44 = 0 or 1
As shown in Figure 9, when S1DCM is ON during operation (STO function is not required) and
S2DCM is OFF (STO function is required), the drive stops outputting and the keypad shows
the STL2 error. However, you cannot reset the STL2 error even if the S2 status is restored (ON)
regardless of the parameter setting. You must cycle the power to reset and to restore the drive
to the normal standby state.
Figure 15-9