EasyManuals Logo
Home>Delta>DC Drives>ME300 Series

Delta ME300 Series User Manual

Delta ME300 Series
457 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #51 background imageLoading...
Page #51 background image
Chapter 7 Optional AccessoriesME300
7-3
Model
Applicable
Motor
*
1
125% Braking Torque 10% ED
Max. Braking Torque
HP kW
*
2
Braking
Torque
(kg-m)
Resistor
Value Spec.
for Each AC
Motor Drive
Brake Resistor for
Each Brake Unit
Braking
Current
(A)
Min.
Resistor
Value
(Ω)
Max. Total
Braking
Current
(A)
Peak
Power
(kW)
*
3
Part No.
Q’ty Usage
VFD7A5ME23ANNAA
VFD7A5ME23ANSAA
2 1.5 1 200W 91Ω BR200W091 1 - 4.2 47.5 8 3.0
VFD11AME23ANNAA
VFD11AME23ANSAA
3 2.2 1.5 300W 70Ω BR300W070 1 - 5.4 38.0 10 3.8
VFD17AME23ANNAA
VFD17AME23ANSAA
5 3.7/4
2.5 400W 40Ω BR400W040 1 - 9.5 19.0 20 7.6
VFD25AME23ANNAA
VFD25AME23ANSAA
7.5 5.5 3.7 1000W 20Ω BR1K0W020 1 19 16.5 23 8.7
Table 7-3
460V three-phase
Model
Applicable
Motor
*
1
125% Braking Torque 10% ED
Max. Braking Torque
HP kW
*
2
Braking
Torque
(kg-m)
Resistor
Value Spec.
for Each AC
Motor Drive
Brake Resistor for
Each Brake Unit
Braking
Current
(A)
Min.
Resistor
Value
(Ω)
Max. Total
Braking
Current
(A)
Peak
Power
(kW)
*
3
Part No.
Q’ty Usage
VFD1A5ME43ANNAA
VFD1A5ME43AFNAA
VFD1A5ME43ANSAA
VFD1A5ME43AFSAA
0.5 0.4 0.3 80W 750Ω BR080W750 1 - 1 380.0 2 1.5
VFD2A7ME43ANNAA
VFD2A7ME43AFNAA
VFD2A7ME43ANSAA
VFD2A7ME43AFSAA
1 0.75
0.5 80W 750Ω BR080W750 1 - 1 190.0 4 3.0
VFD4A2ME43ANNAA
VFD4A2ME43AFNAA
VFD4A2ME43ANSAA
VFD4A2ME43AFSAA
2 1.5 1 200W 360Ω BR200W360 1 - 2.1 126.7 6 4.6
VFD5A5ME43ANNAA
VFD5A5ME43AFNAA
VFD5A5ME43ANSAA
VFD5A5ME43AFSAA
3 2.2 1.5 300W 250Ω BR300W250 1 - 3 108.6 7 5.3
VFD7A3ME43ANNAA
VFD7A3ME43ANSAA
VFD7A3ME43AFNAA
VFD7A3ME43AFSAA
4 3 2 400W 150Ω BR400W150 1
2 in
series
5.1 95.0 8 6.1
VFD09AME43ANNAA
VFD09AME43AFNAA
VFD09AME43ANSAA
VFD09AME43AFSAA
5 3.7/4
2.5 400W 150Ω BR400W150 1 - 5.1 84.4 9 6.8
VFD13AME43ANNAA
VFD13AME43AFNAA
VFD13AME43ANSAA
VFD13AME43AFSAA
7.5 5.5 3.7 1000W 75Ω BR1K0W075 1 - 10.2 50.7 15 11.4
VFD17AME43ANNAA
VFD17AME43AFNAA
VFD17AME43ANSAA
VFD17AME43AFSAA
10 7.5 5.1 1000W 75Ω BR1K0W075 1 - 10.2 40.0 19 14.4
Table 7-4
* 1.
Calculation for 125% brake torque: (kW)*125%*0.8; where 0.8 is motor efficiency.
Because of the limited resistor power, the longest operation time for 10% ED is 10 seconds (ON: 10 sec. / OFF: 90 sec.).
* 2.
The calculation of the brake resistor is based on a four-pole motor (1800 rpm).
* 3.
For heat dissipation, a resistors of 400 W or lower should be fixed to the frame and maintain the surface temperature
below 250°C; a resistor of 1000 W and above should maintain the surface temperature below 350°C.
(If the surface temperature is higher than the temperature limit, install extra cooling or increase the size of the resistor.)
NOTE:
1. Select the resistance value, power and brake usage (ED %) according to Delta rules.
Definition for Brake Usage ED%