Figure 5-26 Constant Q parameters
Figure 5-27 Q(V) page
5.2.8.6. Constant Q
Like Constant cosphi function, users can assign a percentage of reactive
power in Constant Q page.
5.2.8.7. Q(V)
Q(V) is a control mode that inverter will provide reactive power accroding
to grid voltage. For country Italy MV and Italy LV, users can set lock-in
power and lock-out power to assign Q(V) function operation interval.
Constant cosphi
Cosphi (P)
Constant Q
Q(V)
ENT
EXIT
Mode
Fix Q
OFF
Ind 90%
Constant cosphi
Cosphi (P)
Constant Q
Q(V)
ENT
EXIT
EXIT
EXIT
Mode
V1s
V2s
Qs limit
OFF
248.4V
253.0V
Ind 44%
V1i
V2i
Qi limit
T delay
211.6V
207.0V
Cap 44%
10.00s
P lock-in
P lock-out
20%
5%
53