Chapter 12 Description of Parameter SettingsME300
12
.1
-
00
-
12
Select or switch AUTO / HAND mode by using the digital keypad KPC-CC01 (optional) or setting
the multi-function input terminal MI = 41, 42.
The default for Pr.00-29 is 0 (standard Hand-Off-Auto function). Set the AUTO frequency and
operation source with Pr.00-20 and Pr.00-21. Set the HAND frequency and operation source with
Pr.00-30 and Pr.00-31.
When you set the external terminal (MI) to 41 and 42 (AUTO / HAND mode), Pr.00-29 = 1,2,3,4
are disabled. The external terminal has the highest command priority, and Pr.00-29 functions in
standard HOA mode.
When you do not set Pr.00-29 to 0, the Local / Remote function is enabled, and the top right
corner of digital keypad KPC-CC01 (optional) displays LOC or REM. Set the LOCAL frequency
and operation source with Pr.00-20 and Pr.00-21. Set the REMOTE frequency and operation
source with Pr.00-30 and Pr.00-31. Select or switch LOC / REM mode with the digital keypad
KPC-CC01 (optional) or set the multi-function input terminal MI = 56. The AUTO key of the digital
keypad is for the REMOTE function, and HAND key is for the LOCAL function.
When you set the external terminal (MI) to 56 for LOC / REM mode selection, if you set Pr.00-29
to 0, then the external terminal function is disabled.
When you set the external terminal (MI) to 56 for LOC / REM mode selection, if Pr.00-29 is not
set to 0, then AUTO / HAND key is disabled, and the external terminal has the highest command
priority.
The external terminal (MI) set to 56 for LOC / REM selection is valid only when Pr.00-20 Master
Frequency Command Source (AUTO) and Pr.00-21 Operation Command Source (AUTO) are set
to external terminals.
Master Frequency Command Source (HAND)
Default: 0
Settings
0: Digital keypad
1: Communication RS-485 input
2: External analog input (Refer to Pr.03-00)
3: External UP / DOWN terminal
7: Digital keypad dial
Determines the master frequency source in HAND mode.
Operation Command Source (HAND)
Default: 0
Settings 0: Digital keypad
1: External terminals
2: Communication RS-485 input
Select or switch AUTO / HAND mode by using the digital keypad KPC-CC01 (optional) or setting
the multi-function input terminal MI = 41, 42.
Use Pr.00-20 and Pr.00-21 to set the frequency source and the operation source in AUTO mode,
and use Pr.00-30 and 00-31 to set the frequency source and the operation source in HAND
mode.