OUT: 6 VDC, 200 mA maximum
USE ONLY SHUNTED CURRENT TRANSFORMERS (CTs).
Do not use other CTs. Only use shunted CTs with a 333mV maximum output
only. Serious shock hazard and logger damage can occur if unshunted CTs
are used. The UL listing covers the use of the following DENT Instruments
CTs that are UL Recognized and have been evaluated to IEC 61010-1:
CT-HSC-020-X (20A Mini), CT-HSC-050-X (50A Mini), CT-HMC-0100-X (100A
Midi), and the CT-HMC-0200-X (200A Midi). The use of any other CT will
invalidate the UL Listing of the ELITEpro XC.
Pulse: Use only "dry contact" non-energized pulse inputs (ELITEpro SP
only). Use of energized pulse initiators can cause damage to the logger and a
potential shock hazard to the user. Wiring must meet 600V AC CAT III rating.
Equipment protected throughout by double insulation (IEC 536 Class II). CAT
III 80-600 VAC 125mA 50/60 Hz
MAINTENANCE
There is no required maintenance with the ELITEpro XC. Abide by the following items:
Cleaning: No cleaning agents, including water, shall be used on the ELITEpro XC.
Battery Life: The lithium battery is only used to maintain the date and clock settings during power
failure and has a life expectancy of greater than 10 years. Contact DENT Instruments for service.
No accessories are approved for use with the ELITEpro XC other than those specified in the DENT
Instruments product literature and price sheets.
If the logger appears damaged or defective, first disconnect all power and sensors. Call or email
technical support for assistance.