70
For DC Inputs
Note: Input conditioning jumper LJ1, LJ2. or LJ3 needs to be changed, see Appendix A.
INPUT RANGE DISPLAYED CODE
0-20mA 3413
4-20mA 3414
0-50mV 4443
10-50Mv 4499
0-100 mV 4412
0-5V 4445
1-5V 4434
0-10V 4446
2-10V 4450
Remote Setpoint Input Ranges
SECOND INPUT
RANGE
INPUT
RANGE
DISPLAYED
CODE
rSP1 0 - 50mV
10 - 50mV
0 - 100mv
4443
4499
4412
rSP3 0 - 20mA
4 - 20mA
3413
3414
rSP4 0 - 5V
1 - 5V
0 - 10V
2 - 10V
4445
4434
4446
4450
If the Second Input Usage is set to rSP9, the upper display will show the
fixed legend Pot.