On/Off settings
Cold start
Enables the product to be started
on battery power.
First cold start always disabled.
If mains recover during a shutdown
sequence:
- if enabled, shutdown sequence will
complete and wait 10 seconds prior
to restart
- if disabled, shutdown sequence will
not complete and restart will occur
Enables the product to restart
automatically when mains recovers
after a complete battery discharge.
If enabled, UPS will shut down after
5min of back-up time, if no load is
detected on the output.
If disabled, LCD and communication
will turn OFF immediately after
UPS is OFF.
If enabled, LCD and communication
stays ON 1h30 min after UPS is OFF.
If enabled, shutdown or restart commands
from software are authorised.
[0 s] [1s ] [2 s]...[180 s]
Delays remote power off command
[No test] [Every day] [Every week]
[Every month]
Available only if battery charge
mode is set to constant charge.
Every week(in constant charge,
otherwise following ABM
battery test method)
The alarm triggers when the set
percentage of battery capacity is
reached during a back-up time.
Restart battery
level
[1 %] [2 %] ... [100 %]
If set, automatic restart will occur
only when percentage of battery
charge is reached.
[ABM cycling] [Constant charge]
[Auto detection] [Manual EBM set.]
Using standard EBM, UPS
detects automatically the
number of EBM connected
If set to Yes, the UPS automatically
prevents battery from deep
discharge by adapting end of
back-up time voltage threshold.