EasyManuals Logo
Home>Eaton>UPS>9155

Eaton 9155 User Manual

Eaton 9155
92 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #65 background imageLoading...
Page #65 background image
OPERATION
Eaton 9155 UPS (8–15 kVA) User's Guide S 164201553 Rev G (www.eaton.com/powerquality)
59
User Settings
The following table displays the options that can be changed by the user.
NOTE Changes to the output voltage or frequency options should be made before turning on the UPS;
otherwise, the changes do not take effect.
Table 9. User Settings
Description Available Settings Default Setting
Set Date and Time Set Month
Date: mm/dd/yyyy
Time: 24:00
01/01/2003
00:00
Display Contrast Adjust contrast with up/down arrow buttons Moderate
Change Language Select Language: <English>
Elegir idioma <Español>
English
Relay Config Relay: [Alarm 1] [X-Slot 1-1/2/3/4] or [X-Slot 2-1/2/3/4]
Setup: [empty] [On Battery] [Summary Alarm] [On Bypass] [UPS ok]
[custom]
Alarm 1: empty
X-Slots (1 or 2)
#1: UPS ok
#2: On Bypass
#3: Summary Alarm
#4: On Battery
Signal Inputs [empty] [Logic]
(see “Programmable Signal Inputs” on page 56)
<empty>
Serial Port Config Port: [X-Slot-1] [X-Slot-2/Serv]
Speed: [19200] [9600] [2400] [1200]
19200
Parallel Operation Settings Refer to the Eaton 9155 Parallel UPS (8–15 kVA) User's Guide.
Modem Config
Modem Installation <Not Installed>
Set Modem Call Events Event #0
Call modem: no
Set Modem Init String ATZ0
Set Modem Call Command None
Set Modem Communication Password None
Start Screen Eaton logo
Mimic screen
Eaton logo
User Password Enabled/Disabled
If Enabled is selected, the password is USER.
Disabled
Audible Alarms Normal Sound/Disabled Normal Sound
Battery Charging ABM cycling/constant ABM cycling
Automatic Battery Tests Enabled/Disabled
Enabled automatically runs the battery test once a month.
Enabled
Full Power Battery Test Enabled/Disabled Enabled
Number of Battery Strings 0 through 22
(see “Configuring the UPS for EBMs” on page 64)
2 strings for UPS-32 models
4 strings for UPS-64 models
Battery Capacity 1 through 65535 watts per cell 34 W/cell
Battery Low Alarm Level 1.750 through 1.950 volts per cell 1.880 V/cell

Table of Contents

Other manuals for Eaton 9155

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton 9155 and is the answer not in the manual?

Eaton 9155 Specifications

General IconGeneral
BrandEaton
Model9155
CategoryUPS
LanguageEnglish

Related product manuals