SPECIFICATIONS
Eaton 9155 UPS (8–15 kVA) User's Guide S 164201553 Rev G (www.eaton.com/powerquality)
74
Table 13. Dimensions and Weights
Dimensions (H x W x D) Weight
2-High UPS
32.2” 12” 32” (81 30 81 cm)
352 lb (160 kg)
3-High UPS-32
47.8” 12” 32” (121.5 30 81 cm)
550 lb (250 kg)
3-High UPS-64
47.8” 12” 32” (121.5 30 81 cm)
590 lb (268 kg)
2-High EBM
32.2” 12” 30.3” (81 30 77 cm)
480 lb (218 kg)
3-High EBM
47.8” 12” 30.3” (121.5 30 77 cm)
710 lb (322 kg)
PDM (rear UPS mount)
16.5” 12” 7” (42 30 17.8 cm)
25 lb (11 kg)
MBM (rear UPS mount)
16.5” 12” 7” (42 30 17.8 cm)
18 lb (8 kg)
Table 14. Environmental and Safety Specifications
Operating Temperature 50°F to 104°F (10°C to 40°C)
Optimal battery performance: 77°F (25°C)
Transit Temperature -13°F to 131°F (-25°C to 55°C)
Storage Temperature 32°F to 77°F (0°C to 25°C)
Recommended battery storage: 15°C to 25°C (59°F to 77°F)
Ventilation Front air intake, forced air, two fans, positive pressurization,
temperature UPS-monitored
Altitude 9,843 ft (3,000m) operating without derating
32,810 ft (10,000m) during transportation
Relative Humidity 5–95% noncondensing
Heat Dissipation 5582 BTU/hr maximum online
5294 BTU/hr maximum on battery
Audible Noise <56 dBA at 1 meter distance, typical loads
<62 dBA for heavy load, high ambient or high altitude, on battery
Surge Suppression ANSI C62.41 Category B3
Safety Conformance NOM-019-SCFI, UL 1778, CSA C22.2, No. 107.3;
EN 55022 Class A (CISPR22 Class A) and IEC 60950; IEC 62040-1-1
Agency Markings cULus, cUL, CE, NOM-NYCE
EMC (Class A) IEC 62040-2, FCC Part 15, ICES-003, VCCI