SPECIFICATIONS
Eaton 9155 UPS (8–15 kVA) User's Guide S 164201553 Rev G (www.eaton.com/powerquality)
76
Table 16. Model Specifications (continued)
12 kVA Model
Output Voltage (Line–Line) 200 220 240 208 220
Output Voltage (Line–Neutral) 100 110 120 120 127
Input Current* 68A 62A 57A 57A 54A
Output Current 60A 55A 50A 50A 47A
Output kVA (Line–Line Loads) 12.0 12.0 12.0 10.4 10.4
Output kVA (Line–Neutral Loads) 12.0 12.0 12.0 12.0 12.0
Output kW 10.8 10.8 10.8 10.8 10.8
Output Peak Current 132 132 132 132 132
Efficiency (Minimum) 88% 88% 88% 88% 88%
Power Dissipation (BTU/hr) 4512 4512 4512 4512 4512
DC Voltage (Supply) 192 192 192 192 192
10 kVA Model
Output Voltage (Line–Line) 200 220 240 208 220
Output Voltage (Line–Neutral) 100 110 120 120 127
Input Current* 57A 52A 48A 48A 45A
Output Current 50A 45A 42A 42A 39A
Output kVA (Line–Line Loads) 10.0 10.0 10.0 8.7 8.7
Output kVA (Line–Neutral Loads) 10.0 10.0 10.0 10.0 10.0
Output kW 9.0 9.0 9.0 9.0 9.0
Output Peak Current 110 110 110 110 110
Efficiency (Minimum) 87% 87% 87% 87% 87%
Power Dissipation (BTU/hr) 4175 4175 4175 4175 4175
DC Voltage (Supply) 192 192 192 192 192
8 kVA Model
Output Voltage (Line–Line) 200 220 240 208 220
Output Voltage (Line–Neutral) 100 110 120 120 127
Input Current* 46A 42A 38A 38A 36A
Output Current 40A 36A 33A 33A 31A
Output kVA (Line–Line Loads) 8.0 8.0 8.0 6.9 6.9
Output kVA (Line–Neutral Loads) 8.0 8.0 8.0 8.0 8.0
Output kW 7.2 7.2 7.2 7.2 7.2
Output Peak Current 88 88 88 88 88
Efficiency (Minimum) 87% 87% 87% 87% 87%
Power Dissipation (BTU/hr) 3300 3300 3300 3300 3300
DC Voltage (Supply) 192 192 192 192 192
* Input current for the input isolation transformer is 4% higher than for the UPS.