Eaton 93E UPS 15-80 kVA (380/400/415 V) Installation and Operation Manual
© Eaton Corporation plc 2015. All rights reserved. Revision: 001
Document ID: 614-01975-00
41 (133)
• The UPS requires an input neutral connection. Make sure that an
input neutral is connected prior to energizing the UPS. If a 4-pole
automatic transfer switch is installed upstream of the UPS, it must
work with a break before make transition for the phase wires with a
minimum transfer time of 50 ms. Neutral must work with a make
before break transition.
Figure 15 and Figure 16 show the location of the UPS power cable
terminals.
Table 5. Input / output ratings and external cabling recommendations for the
Eaton 93E 15-80 kVA
Volts
400/
415
400/
415
400/
415
400/
415
400/
415
400/
415
A: AC Input to UPS rectifier (0.99
minimum PF)
Full load current plus battery
recharge current (3) phases
Amps
23 31 46 61 92 123
Conductor size
(phase L1, L2,
L3, N)
Recommended
Maximum *
B: AC input to UPS bypass (5-wire,
dual feed)
Full load current, (3) phases
Conductor size
(phase L1, L2,
L3, N)
Recommended
Maximum *
C: DC input from external battery
(384 V)
(1) positive, (1) negative
Amps
Conductor size Recommended
Maximum *