Input current harmonic content
6 kV OC, 3 kA SC per ANSI 62.41 and
IEC 8014
384 Vdc (32 blocks) if using internal
batteries.
384-480 Vdc (32-40 blocks) if using
external batteries.
Do not connect battery strings
with different number of cells in
parallel!
Battery charging capacity (384 Vdc)
load up to a 100% load
load up to a 100% load
load up to a 100% load
any load up to a 100%
load
load up to a 100% load
load up to a 100% load
10.2.4 UPS output
Output voltage regulation
380 Vac, 400 Vac and 415 Vac nominal
Output voltage harmonic content
2% maximum THD (linear load)
5% maximum THD (non-linear load)