Page 14
9PX-6K-SP_EN
3. Installation for 9PX 6K SP
3.6 Connecting the internal battery
Do not make unauthorized changes to the UPS; otherwise, damage may occur to your equipment
and void your warranty. Do not connect the UPS to utility until installation is completed.
This step requires two people, the UPS and internal battery are heavy.
Description Weights (lb/kg)
9PX 6K SP without internal battery 73 / 33
9PX 6K SP internal battery 23 / 10.5
1
2
3
4
5
6
7
8
• Mount the UPS on rack.
• Remove the center cover of the front panel.
• Remove the two screws to open the left side of the front panel.
• Remove the 1U bottom part by using the latch button.
• Remove the one screw to pull out the metal protection cover of the battery.
• Put the battery pack, screw back the metal protection cover, connect the battery and put back the
front panel, then clip the center cover.
A ribbon cable connects the LCD control panel to the UPS. Do not pull on the cable or disconnect it.
A small amount of arcing may occur when connecting the internal batteries. This is normal and will
not harm personnel. Connect the cables quickly and firmly.
Battery connectors may be coupled
to either battery pack.