14 OPERATION AND INSTALLATION INSTRUCTIONS MN280075EN July 2018
Form 6 microprocessor-based rack-mount recloser control
The control is designed to be mounted in a standard19"
substation rack. There are three available mounting
accessories available:
Double rack mount accessory with two handles and one
connecting plate.
Single rack mount accessory with two handles.
Double rack – single mount accessory with two handles
and one filler plate.
Refer to Accessories section of this manual for accessory
attachment instructions.
CONTROL WEIGHT: 7 kg (15 lbs)
ote:N Weight of one Form 6 rack mount recloser control
with handles attached to both sides.
19 (.75)
229 (9)
254 (10)
38
(1.5)
184
(7.25)
222
(8.75)
220 (8.75)
262 (10.25)
245 (9.75)
.32 x .41 Dia. Mounting Holes (4)
Grounding Terminal
0.25 x 20 x 0.75 LG
Side View
Front View
22 (.87)
88 (3.5)
88 (3.5)
10-32 Tapped Holes
3 Places on Each Side
Optional Handles (2)
CONTROL POWER
CONTROL OK
CONTROL LOCKOUT
RECLOSER OPEN
RECLOSER CLOSED
A PHASE FAULT
B PHASE FAULT
C PHASE FAULT
GROUND FAULT
SENSITIVE GND
ALARM
ABOVE MIN TRIP
INDICATOR 1
INDICATOR 2
INDICATOR 3
A PHASE VOLTAGE
B PHASE VOLTAGE
C PHASE VOLTAGE
FREQUENCY TRIP
VOLTAGE TRIP
METERING
RESET
TARGETS
EVENTS
LAMP TEST
MENU
ENTER
+
SETTINGS
OPER
COUNTER
ALARMS
CHANGE
F1 F2 F3 F4
TRIP CLOSE
HOT LINE TAG
ON
GND TRIP
BLOCKED
NON
RECLOSING
SUPERVISORY
OFF
ALTERNATIVE
PROFILE #1
ALTERNATIVE
PROFILE #2
ALTERNATIVE
PROFILE #3
RS-232 DATA PORT
OPTION #1
OPTION #2
OPTION #3
(LOCKOUT)
INDICATOR 4
INDICATOR 5
INDICATOR 6
INDICATOR 7
INDICATOR 8
CLOSE CIRCUIT
DISABLE
COOPER POWER
SERIES
Figure8. Form 6 rack mount recloser control weight and dimensions
Grounding the control
WARNING
Hazardous voltage. Recloser and control must
be solidly grounded. Follow all locally approved
procedures and safety practices when grounding this
equipment. Improper grounding can result in contact
with high voltage, which will cause death or severe
personal injury. G115.1
The Form 6 rack mount recloser control must be solidly
grounded prior to installation or energization. Refer to
Figure9 for grounding connections.
ote:N Grounding of the mounting panel or
standard19" rack does not eliminate the control
grounding requirement.
The grounding connection on the back of the control will
accommodate a spade connector or ring terminal that fits
on a .25 inch diameter grounding terminal stud (Figure10).
ote:N Control grounding must comply with all locally
approved procedures and safety practices that apply
in a substation or other appropriate indoor facility.
The recloser that the control will be connected to must also
be properly grounded per the grounding requirements of the
individual recloser. Refer to the appropriate installation and
operation manual for grounding requirements.
IMPORTANT
All external wiring inputs to the Form 6 recloser control
must be routed within 8 inches of their corresponding
ground. During a surge, a potential of approximately 1.5
kV per foot can develop in the conductors. Differences
between conductor and ground path lengths can add
additional stress to the control components in the event of
a power surge.