EasyManuals Logo
Home>Eaton>Control Unit>Form 6

Eaton Form 6 User Manual

Eaton Form 6
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #31 background imageLoading...
Page #31 background image
27OPERATION AND INSTALLATION INSTRUCTIONS MN280075EN July 2018
Form 6 microprocessor-based rack-mount recloser control
Accessories
These accessories are available. Contact your Eaton
representative for additional information.
Control cable
The control cable consists of two separate wire sizes
pending the distance from the Form 6 recloser control
to the selected Eaton Cooper Power series recloser. The
control cable is fabricated with a connector on one end
and pigtailed on the other. The connector is mated to
the recloser receptacle on one end and hardwired to the
control on the other end. Refer to Table3 in the Recloser
Connection/Control Cable section of this manual for
available control cable lengths.
Recloser interface junction box
The recloser interface junction box (mounted on a recloser
substation frame) facilitates customer wiring from the
recloser to the control. The junction box is required when
the distance between the recloser and control exceeds the
maximum available control cable length for the KA85ME
control cable (Table3).
There are two types of junction boxes available:
KME6-1811 The recloser interface junction box cable is
factory-hardwired between the recloser and the junction
box. Refer to Figure21, Figure22, and Figure25.
KME6-1859 The recloser interface junction box cable
disconnects at both ends. The junction box has a male
receptacle that enables connection between the recloser
and the junction box with existing control cables from
other Eaton Cooper Power series controls (Form 3A,
Form 4C, etc.). Refer to Figure23, Figure24, and
Figure26.
The junction box is mounted on the substation frame based
upon the mounting dimensions in Figure21 or Figure23.
The junction box cabinet includes multiple diameter holes
for sealing grip connections to hardwire to the control.
A recloser interface junction box cable connects from
the junction box to the recloser (Figure22 or Figure24).
Refer to Figure25 or Figure26 for control-to-junction
box customer connection diagrams. Refer to Table10 for
control-to-junction box cable requirements.
203 mm
(8.0 in)
254 mm
(10.0 in)
1.062 dia. Hole for
Junction Box Cable
(factory-hardwired)
1.312 dia. Hole
(capped)
152 mm
(6.0 in)
.312 diameter
Mounting Hole (4)
109 mm
(4.25 in)
1.062 dia. Hole (2)
(capped)
273 mm
(10.75 in)
101.5 mm
(4.0 in)
.41 diameter
Mounting Hole (2)
292 mm
(11.5 in)
Figure21. Form 6 recloser interface junction box KME6-1811 dimensions mm (in). (Dimensions are approximate.)

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton Form 6 and is the answer not in the manual?

Eaton Form 6 Specifications

General IconGeneral
BrandEaton
ModelForm 6
CategoryControl Unit
LanguageEnglish

Related product manuals