UPS MAINTENANCE
Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev D www.eaton.com/powerquality
96
To transfer the load from the UPS to maintenance bypass:
1. Set the system to internal Bypass mode:
S Using the button on the front panel display, scroll to the Control
menu option and press the
button.
S Press the button to select the Go to Bypass Mode option.
The
indicator illuminates and the indicator extinguishes,
indicating the UPS system is operating in Bypass mode.
2. Turn the maintenance bypass switch to the BYPASS position.
The battery circuit breaker trips, and the UPS is now bypassed, with
the load powered by utility power.
3. The UPS automatically shuts down.
To transfer the load from maintenance bypass to the UPS:
1. Turn the maintenance bypass switch to the SERVICE position.
The UPS starts up in Bypass mode, with the load still powered by
utility power.
2. Switch the UPS input and battery circuit breakers to the ON
position.
NOTE Wait until the indicator illuminates before proceeding to Step 3; otherwise,
power to the load may be lost.
3. Turn the maintenance bypass switch to the UPS position to return
to Normal mode.
The UPS is now powering the load.