COMMUNICATION
Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev D www.eaton.com/powerquality
75
Table 6. IRC Wire Terminations
IRC Terminal Function Remarks
J2-1 NC
Normal mode
J2-2 COM
J2-3 NO
J2-4 NC
Bypass mode
J2-5 COM
J2-6 NO
J2-7 NC
Battery mode
J2-8 COM
J2-9 NO
J2-10 NC
Alarm mode
J2-11 COM
J2-12 NO
NOTE Maximum contact rating: 250 Vac, 30 Vdc @ 5A; Wire range: 16–24 AWG
LanSafe Power Management Software
Each Eaton 9355 UPS UPS ships with LanSafe Power Management
Software and an interface cable. To begin installing LanSafe software,
see the instructions accompanying the Software Suite CD.
NOTE Use only the supplied communication cable to connect the UPS to your computer.
LanSafe software provides up-to-date graphics of UPS power and
system data and power flow. It also gives you a complete record of
critical power events, and it notifies you of important UPS or power
information. If there is a power outage and the Eaton 9355 UPS UPS
battery power becomes low, LanSafe software can automatically shut
down your computer system to protect your data before the UPS
shutdown occurs.