SPECIFICATIONS
Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev D www.eaton.com/powerquality
100
Table 11. Dimensions and Weights
Dimensions (H W D)
Weight
2-High UPS
32.2” 12” 33.5” (81 30 85 cm)
381 lb (173 kg)
3-High UPS-32
47.8” 12” 33.5” (121.5 30 85 cm)
587 lb (266 kg)
3-High UPS-64
47.8” 12” 33.5” (121.5 30 85 cm)
619 lb (281 kg)
2-High EBM
32.2” 12” 30.3” (81 30 77 cm)
480 lb (218 kg)
3-High EBM
47.8” 12” 30.3” (121.5 30 77 cm)
710 lb (322 kg)
Table 12. Environmental and Safety Specifications
Operating Temperature 50°F to 104°F (10°C to 40°C)
Optimal battery performance: 77°F (25°C)
Transit Temperature -13°F to 131°F (-25°C to 55°C)
Storage Temperature 32°F to 77°F (0°C to 25°C)
Recommended battery storage: 59°F to 77°F (15°C to 25°C)
Ventilation Front air intake, forced air, two fans, positive pressurization,
temperature UPS-monitored
Altitude 9,843 ft (3,000m) operating without derating
32,810 ft (10,000m) during transportation
Relative Humidity 5–95% noncondensing
Audible Noise <56 dBA at 1 meter distance, typical loads
<62 dBA for heavy load, high ambient or high altitude, on battery
Surge Suppression ANSI C62.41 Category B3
Safety Conformance NOM-019-SCFI, UL 1778, CSA C22.2, No. 107.3;
EN 55022 Class A (CISPR22 Class A) and IEC 60950; IEC 62040-1-1
Agency Markings cULus, cUL, CE
EMC (Class A) IEC 62040-2, FCC Part 15, ICES-003