3 Initial connection and configuration
To configure the gateway, a local connection between a computer and the
gateway needs to be established.
Powering the Gateway
For the Emerson Wireless 1410S Gateway, bench top power will be needed
to power the Gateway by wiring a 10.5–30 VDC power source.
An Emerson Wireless 1410S Gateway can also be powered via Power over
Ethernet (PoE) and is compliant with the IEEE 802.3af standard.
Note
The Emerson Wireless 1410S2 Gateway hardware revision 1.0.0 configured
with Intrinsically Safe Outputs option “A” can only be powered by 24 VDC
power source. Check label to verify hardware revision.
July 2022 Quick Start Guide
Quick Start Guide 7