Epsilon Eb and EN Drives Reference Manual
Velocity Test
1. Disable the drive.
2. Select Velocity Analog mode and set "Full Scale Velocity" parameter to 12 RPM.
3. Use the simulator to adjust the analog command voltage to 5 volts.
4. Enable the drive. Find the "Velocity Command Analog" parameter on the Status tab.
Adjust the analog command until this parameter reads exactly 6 RPM. The motor should
be moving at 6 RPM. If the system got through the Torque test, the motor should not run-
away at this point. If it does, go back and repeat the Torque test.
5. Confirm that the motor velocity is really 6 RPM by confirming that it takes 10 seconds
to make one revolution. If this is not the case, the problem may be that both the motor
poles and the encoder line density are off by the same factor.
6. Reduce the analog command voltage to zero volts and disable the drive.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Control Techniques Epsilon Eb Series and is the answer not in the manual?

Emerson Control Techniques Epsilon Eb Series Specifications

General IconGeneral
BrandEmerson
ModelControl Techniques Epsilon Eb Series
CategoryDC Drives
LanguageEnglish

Related product manuals