1592040000 XR20-30-60-70T EN v1.5 2021.06.22 XR20-30-60-70T 20/41
PAr
Parity control: (no; odd; EvE) no=no parity control; odd=odd parity control; EvE=even parity
control
5.1.15 User Interface configuration parameters - Ui
b3C
Button 3 configuration: (nu; AUS; MAP) function linked to button 3. AUS=auxiliary output
control; MAP=parameter map change.
b1F
Button 1 enabled in stand-by: (n; Y)
SCS
User interface timeout: (1 to 255 sec) timeout before coming back to Home Screen or to
Programming Menu
bS
Sound Level: (0 to 5) select the sound level of the gestures
PSU
Password for protected level Pr2: (000 to 999) insert a value to protect all the parameters set
on the level Pr2 from modification
5.1.16 Information, read only parameters - inF
dP1
Probe P1 value visualization
dP2
Probe P2 value visualization
dP3
Probe P3 value visualization
dP4
Probe P4 value visualization
rSE
Real regulation Set Point
FdY
Firmware release date: day
FMt
Firmware release date: month
FYr
Firmware release date: year
rEL
Firmware release: progressive number
SUb
Firmware sub release: progressive number
Ptb
Parameter map version
NOTE: some parameters are not present in models XR30T and XR60T due to lack of the relevant I/O’s.
5.2 PARAMETER CONFIGURATION 1
Group
Par.
Description
Value
Protected
U.O.M.
Range
rEG
SEt
Set Point
3.0
Pr1
°C
LS to US
rEG
LS
Minimum Set point
-100.0
Pr1
°C
[-100.0°C to SET]
[-148.0°F to SET]
rEG
US
Maximum Set point
150.0
Pr1
°C
[SET to 150.0°C]
[SET to 302.0°F]
rEG
HY
Compressor regulation differential in
normal mode
3.0
Pr1
°C
[0.1°C to 25.0°C]
[0.1°F to 45.0°F]
rEG
HYE
Compressor regulation differential in
energy saving mode
3.0
Pr1
°C
[0.1°C to 25.0°C]
[0.1°F to 45.0°F]
rEG
HY1
Second Compressor regulation differential
in normal mode
3.0
Pr2
°C
[0.1°C to 25.0°C]
[0.1°F to 45.0°F]
rEG
HYS
Second Compressor regulation differential
in energy saving mode
5.0
Pr2
°C
[0.1°C to 25.0°C]
[0.1°F to 45.0°F]
rEG
HYd
Deadband output regulation (oAx=db)
differential
2.0
Pr2
°C
[0.1°C to 25.0°C]
[0.1°F to 45.0°F]
rEG
rAr
Delay between compressor and db output
(oAx=db) activation and vice versa
0
Pr2
min
0 to 255 min
rEG
odS
Output activation delay at start-up
0
Pr1
min
0 to 255 min
rEG
AC
Anti-short cycle delay
0
Pr1
min
0 to 50 min
rEG
AC1
Anti-short cycle delay (2nd compressor)
0
Pr2
sec
0 to 255 sec
rEG
2CC
Activation mode for 2nd compressor:
HAF=step logic; FUL=delayed
FUL
Pr2
rEG
rCC
Enable compressor rotation
no
Pr2
rEG
MCo
Maximum time with compressor on
(0=disabled)
0
Pr2
min
0 to 255 min
rEG
Cdd
Compressor selection during any defrost
cycle
2C
Pr2
rEG
rtr
Regulation percentage=F(P1; P2)
(100=P1; 0=P2)
100
Pr2
0 to 100

Table of Contents

Other manuals for Emerson Dixell XR70T

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Dixell XR70T and is the answer not in the manual?

Emerson Dixell XR70T Specifications

General IconGeneral
BrandEmerson
ModelDixell XR70T
CategoryController
LanguageEnglish

Related product manuals