1592040000 XR20-30-60-70T EN v1.5 2021.06.22 XR20-30-60-70T 39/41
18. TECHNICAL SPECIFICATIONS
Front fascia 38x80 mm; case depth 81mm
Panel, 71x29mm panel cut-out
Indoor use only, Type 1 enclosure
230Vac 10%, 50/60Hz; 110Vac 10%, 50/60Hz; 100 to 240VAC10%, 50/60Hz
12VAC: 3VA; 110VAC: 4VA; 230VAC: 4VA; 100-240VAC: 3VA
White display, LED type, 3 digits with decimal point and multi-function icons
Terminal blocks / Terminal
Connections
Plug-in or screw terminal block, wire section between 0,5 and 2,5 mm
2
Max tightening force: 0.3 N/m for 3,5mm pitch, 0.4 N/m for 5,0mm pitch
Real Time Clock: Data maintenance up to 6 months with lithium battery. Other parameters: internal flash.
2, non-condensing humidity
Ambient Operating Temperature
and Humidity
0T60°C; 20-85 rH% (non-condensing humidity)
-20T60°C; 20-85 rH% (non-condensing humidity)
Shipping and storage
temperature
-40T85°C; 20-85 rH% (non-condensing humidity)
NTC: -40T110°C, resolution 0.1°C or 1°C (selectable); PT1000: -100T150°C, resolution 0.1°C or 1°C (selectable);
PTC: -50T150°C, resolution 0.1°C or 1°C (selectable)
±1% compared to the full scale
Up to 4 NTC, PTC or PT1000 (configurable); Up to 2 voltage free contacts
Resistive load 12A (NO), 230Vac, 50K cycles
Motor load 240Vac (NO), 10FLA/60LRA, 30K
cycles
Pilot Duty B300 (NO), 6K cycles
10(4)A (NO), 230Vac, 100K cycles
Resistive load 10A (NO), 120/240Vac, 30K cycles
Motor load ½ HP (NO), 240Vac, 30K cycles
Motor load ¼ HP (NO), 120Vac, 30K cycles
Pilot duty B300 (NO), 30K cycles
8(3)A (NO), 230Vac, 50K cycles
Resistive load 5A, 120/240Vac, 50K cycles
Motor load 240Vac, 1.9FLA/11.4LRA, 30K cycles
Pilot Duty B300, 30K cycles
5(1)A, 230Vac, 50K cycles
Resistive load 10A (NO), 120/240Vac, 30K cycles
Motor load ½ HP (NO), 240Vac, 30K cycles
Motor load ¼ HP (NO), 120Vac, 30K cycles
Pilot duty B300 (NO), 30K cycles
8(3)A (NO), 230Vac, 50K cycles
Maximum ampacity on common
terminal “Line” (for oAx)
HOT-KEY: MAX voltage allowed is 5 VDC. DO NOT CONNECT ANY EXTERNAL POWER SUPPLY
Incorporated control, intended to be used in Class I or Class II equipment
R290/R600a: relays tested according to IEC EN60079:0 and IEC EN60079:15
IEC/EN 60730-1; IEC/EN 60730-2-9
UL 60730-1; UL 60730-2-9
CAN/CSA E60730-1; CAN/CSA E60730-2-9