OI_EC2-XC645CX_A1_A2L_A3_EN_Rev01_866933.docx EC2-XC645CX 46/54
CODE MEANING CAUSE ACTION RESET
switch alarm
switch input
enabled.
are turned off.
All fans are
turned on.
Automatically (if the number of activations is
less than PEn in the PEi time) when the input
is disable.
- Compressors and fans restart working
according to the working algorithm.
Manually (if PEn activation happened in the
PEi time)
When the input is disable:
a. hold pressed the Restart (DOWN) key for
3 seconds or
b. turn off and on the instrument.
- Compressors and fans restarts working
according to the working algorithm.
failure alarm
out of range.
compressors
are activated
according to the
SPr or PoPr
Automatically as soon as the probe restarts
working.
failure alarm
out of range.
activated
according to the
Automatically as soon as the probe restarts
working.
failure alarm
out of range.
related to the
third probe are
Automatically as soon as the probe restarts
working.
failure alarm
or out of range.
related to the
fourth probe are
Automatically as soon as the probe restarts
working.
EA2
EA3
EA4
EA6
alarm
compressor/fan
input activation.
compressors 1
input for each
compressor has
to be used.
corresponding
load is turned
off. (with step
compressors all
relays referred
to the input are
Recovery depends on ALMr parameter:
With ALMr = no The instrument restart the
standard operating mode when the input is
disabled.
With ALMr = yES manual recover for the
alarms of compressors and fans. Push the
DOWN key for 3 seconds.
pressure
(temperature)
alarm
compressors
pressure or
temperature
lower than
LAL value.
Automatically: as soon as the pressure or
temperature reaches the (LAL+ differential)
value.
(differential = 0.3 bar or 1°C)
pressure
(temperature)
alarm fans
pressure or
temperature
lower than
Automatically: as soon as the pressure or
temperature reaches the (LAF+ differential)
value.
(differential = 0.3 bar or 1°C)
pressure
(temperature)
alarm
compressors
pressure or
temperature
higher than
HAL value.
Automatically: as soon as the pressure or
temperature reaches the (HAL - differential)
value.
(differential = 0.3 bar or 1°C)