OI_EC2-XC645CX_A1_A2L_A3_EN_Rev01_866933.docx EC2-XC645CX 46/54
CODE MEANING CAUSE ACTION RESET
E0H
High pressure
switch alarm
High pressure
switch input
enabled.
All compressors
are turned off.
All fans are
turned on.
Automatically (if the number of activations is
less than PEn in the PEi time) when the input
is disable.
- Compressors and fans restart working
according to the working algorithm.
Manually (if PEn activation happened in the
PEi time)
When the input is disable:
a. hold pressed the Restart (DOWN) key for
3 seconds or
b. turn off and on the instrument.
- Compressors and fans restarts working
according to the working algorithm.
P1
P1 probe
failure alarm
Probe failure or
out of range.
The
compressors
are activated
according to the
SPr or PoPr
parameters.
Automatically as soon as the probe restarts
working.
P2
P2 probe
failure alarm
Probe failure or
out of range.
The fans are
activated
according to the
FPr parameters.
Automatically as soon as the probe restarts
working.
P3
P3 probe
failure alarm
Probe failure or
out of range.
The functions
related to the
third probe are
disabled.
Automatically as soon as the probe restarts
working.
P4
P4 probe
failure alarm
Probe 4 failure
or out of range.
The functions
related to the
fourth probe are
disabled.
Automatically as soon as the probe restarts
working.
EA1
EA2
EA3
EA4
EA6
Load safeties
alarm
Safeties
compressor/fan
input activation.
NOTE: with step
compressors 1
input for each
compressor has
to be used.
The
corresponding
load is turned
off. (with step
compressors all
relays referred
to the input are
disabled).
Recovery depends on ALMr parameter:
With ALMr = no The instrument restart the
standard operating mode when the input is
disabled.
With ALMr = yES manual recover for the
alarms of compressors and fans. Push the
DOWN key for 3 seconds.
C1-LA
Minimum
pressure
(temperature)
alarm
compressors
section
Suction
pressure or
temperature
lower than
LAL value.
Signaling only
Automatically: as soon as the pressure or
temperature reaches the (LAL+ differential)
value.
(differential = 0.3 bar or 1°C)
F-LA
Minimum
pressure
(temperature)
alarm fans
section
Condensing
pressure or
temperature
lower than
LAF value.
Signaling only
Automatically: as soon as the pressure or
temperature reaches the (LAF+ differential)
value.
(differential = 0.3 bar or 1°C)
C1-HA
Maximum
pressure
(temperature)
alarm
compressors
section
Suction
pressure or
temperature
higher than
HAL value.
Signaling only
Automatically: as soon as the pressure or
temperature reaches the (HAL - differential)
value.
(differential = 0.3 bar or 1°C)

Other manuals for Emerson EC2-XC645CX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson EC2-XC645CX and is the answer not in the manual?

Emerson EC2-XC645CX Specifications

General IconGeneral
BrandEmerson
ModelEC2-XC645CX
CategoryController
LanguageEnglish

Related product manuals