OI_EC2-XC645CX_A1_A2L_A3_EN_Rev01_866933.docx EC2-XC645CX 50/54
CODE VALUE MENUE DESCRIPTION RANGE
3P04 -0.5 Pr2
4 mA or 0.5 V readout for P3
probe
3P04 - 885 PSI;
3P20 11.0 Pr2
20 mA or 4.5 V readout for P3
probe
-12.0 - 12.0°C; -20 - 20°F;
-12.0 - 12.0 bar; -200 - 200 PSI;
O3 0.0 Pr2
P3 probe offset
-12.0 - 12.0°C; -20 - 20°F;
-12.0 - 12.0 bar; -200 - 200 PSI;
P4C nP Pr2
P4 probe setting (NTC 10K, NTC
86K)
nP, nt10, nt86
-12.0 - 12.0°C; -20 - 20°F
iF01 OA1 Pr2
Function 1 configurable digital
input
Nu, OA1, OA2, OA3, OA4, OA5,
OA6, InF, LP1, LP2, HP, ES, OFF,
LL, SIL, EAL, Co1, Co2, Co3, Co4,
iF02 OA2 Pr2
Function 2 configurable digital
input
Nu, OA1, OA2, OA3, OA4, OA5,
OA6, InF, LP1, LP2, HP, ES, OFF,
LL, SIL, EAL, Co1, Co2, Co3, Co4,
iF03 OA3 Pr2
Function 3 configurable digital
input
Nu, OA1, OA2, OA3, OA4, OA5,
OA6, InF, LP1, LP2, HP, ES, OFF,
LL, SIL, EAL, Co1, Co2, Co3, Co4,
iF04 OA4 Pr2
Function 4 configurable digital
input
Nu, OA1, OA2, OA3, OA4, OA5,
OA6, InF, LP1, LP2, HP, ES, OFF,
LL, SIL, EAL, Co1, Co2, Co3, Co4,
iF05 LP1 Pr2
Function 5 configurable digital
input
Nu, OA1, OA2, OA3, OA4, OA5,
OA6, InF, LP1, LP2, HP, ES, OFF,
LL, SIL, EAL, Co1, Co2, Co3, Co4,
iF06 HP Pr2
Function 6 configurable digital
input
Nu, OA1, OA2, OA3, OA4, OA5,
OA6, InF, LP1, LP2, HP, ES, OFF,
LL, SIL, EAL, Co1, Co2, Co3, Co4,
iF07 LL Pr2
Function 7 configurable digital
input
Nu, OA1, OA2, OA3, OA4, OA5,
OA6, InF, LP1, LP2, HP, ES, OFF,
LL, SIL, EAL, Co1, Co2, Co3, Co4,
iP01 cL Pr2
Safety input for Load 1 polarity
(13-14):
OP, CL
iP02 cL Pr2
Safety input for Load 2 polarity
(13-15):
OP, CL
iP03 cL Pr2
Safety input for Load 3 polarity
(16-17):
OP, CL
iP04 cL Pr2
Safety input for Load 4 polarity
(16-18):
OP, CL
iP05 cL Pr2
Safety input for Load 5 polarity
(16-18):
OP, CL
iP06 cL Pr2
Safety input for Load 6 polarity
(16-18):
OP, CL
iP07 cL Pr2
Configurable digital input i1F
polarity (22 - 23):
OP, CL
d1d 0 Pr2
Digital input delay for i1F = oA1
or Co1
0 - 255 s
d2d 0 Pr2
Digital input delay for i2F = oA1
& Co1
0 - 255 s