Introduction and Specifications
September 2013
1-5
Table 1-2. Specifications
Available Configurations
DVC6010: Sliding-stem applications
DVC6020: Rotary and long-stroke sliding-stem
applications [over 102 mm (4 inch) travel]
DVC6030: Quarter-turn rotary applications
Remote-Mounted Instrument
(1)
DVC6005: Base unit for 2 inch pipestand or wall
mounting
DVC6015: Feedback unit for sliding-stem
applications
DVC6025: Feedback unit for rotary or long-stroke
sliding-stem applications
DVC6035: Feedback unit for quarter-turn rotary
applications
DVC6000 digital valve controllers can be mounted
on Fisher and other manufacturers rotary and
sliding-stem actuators.
Input Signal
Point-to-Point:
Analog Input Signal: 4-20 mA DC, nominal
Minimum Voltage Available at instrument terminals
must be 10.5 volts DC for analog control, 11 volts
DC for HART communication
Minimum Control Current: 4.0 mA
Minimum Current w/o Microprocessor Restart:
3.5 mA
Maximum Voltage: 30 volts DC
Overcurrent Protection: Input circuitry limits current
to prevent internal damage.
Reverse Polarity Protection: No damage occurs
from reversal of loop current.
Multi-drop:
Instrument Power: 11-30 volts DC at approximately
8 mA
Reverse Polarity Protection: No damage occurs
from reversal of loop current.
Output Signal
Pneumatic signal as required by the actuator, up to
full supply pressure.
Minimum Span: 0.4 bar (6 psig)
Maximum Span: 9.5 bar (140 psig)
Action: Double, Single direct, and Single reverse
Supply Pressure
(2)
Recommended: 0.3 bar (5 psi) higher than
maximum actuator requirements, up to maximum
supply pressure
Maximum: 10 bar (145 psig) or maximum pressure
rating of the actuator, whichever is lower
Medium: Air or Natural Gas
Air: Supply pressure must be clean, dry air that
meets the requirements of ISA Standard 7.0.01.
Natural Gas: Natural gas must be clean, dry,
oil-free, and noncorrosive. H
2
S content should not
exceed 20 ppm.
A maximum 40 micrometer particle size in the air
system is acceptable. Further filtration down to 5
micrometer particle size is recommended. Lubricant
content is not to exceed 1 ppm weight (w/w) or
volume (v/v) basis. Condensation in the air supply
should be minimized
Steady-State Air Consumption
(3)(4)
Standard Relay:
At 1.4 bar (20 psig) supply pressure: Less than 0.38
normal m
3
/hr (14 scfh)
At 5.5 bar (80 psig) supply pressure: Less than 1.3
normal m
3
/hr (49 scfh)
Low Bleed Relay:
At 1.4 bar (20 psig) supply pressure: Average value
0.056 normal m
3
/hr (2.1 scfh)
At 5.5 bar (80 psig) supply pressure: Average value
0.184 normal m
3
/hr (6.9 scfh)
Maximum Output Capacity
(3)(4)
At 1.4 bar (20 psig) supply pressure: 10.0 normal
m
3
/hr (375 scfh)
At 5.5 bar (80 psig) supply pressure: 29.5 normal
m
3
/hr (1100 scfh)
Independent Linearity
(5)
±0.50% of output span
Electromagnetic Compatibility
Meets EN 61326-1 (First Edition)
Immunity—Industrial locations per Table 2 of the
EN 61326-1 standard. Performance is shown
in table 1-3 below.
Emissions—Class A
ISM equipment rating: Group 1, Class A
Lightning and Surge Protection—The degree of
immunity to lightning is specified as Surge immunity
in table 1-3. For additional surge protection
commercially available transient protection devices
can be used.
-continued-
1

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Fisher FIELDVUE DVC6000 and is the answer not in the manual?

Emerson Fisher FIELDVUE DVC6000 Specifications

General IconGeneral
BrandEmerson
ModelFisher FIELDVUE DVC6000
CategoryController
LanguageEnglish

Related product manuals