Backing up and restoring a configuration
4 Backing up and restoring a configuration
Backup configuration
After you have made adjustments to satisfy customer
requirements, you should save the configuration. This
backup saves the configuration, parameter settings,
input and output terminal allocations, etc. – in other
words, all relevant data and settings in the ETAtouch
control system. This makes it possible to quickly
restore the original settings.
Backup configuration
1. In the system settings, increase the authoriza-
tion to [Service], and open the system configura-
tion menu with the [Systems configuration] button.
Fig. 4-1: System configuration menu
2. The backup is started by pressing the [Configura-
tion save] button. Once this is finished, a
message appears on the screen prompting an
additional backup to a USB stick. If you wish to do
this, insert the USB stick into the port on the boiler
and perform the backup.
Restoring the configuration
You can restore the heating system configuration at
any time. The configuration is restored either from a
configuration saved in the ETAtouch control system or
via a USB stick. The counter readings are not
overwritten by this.
Control systems in a wall mounted box are
supplied with a USB stick for backing up the con-
figuration. Leave this in the wall mounted box after you
have restored the configuration.
Restoring the configuration
1. In the system settings, increase the authoriza-
tion to [Service], and open the system configura-
tion menu with the [Systems configuration] button.
To restore a configuration, press the [Configura-
tion restore] button. Another menu appears:
Fig. 4-2: Restore menu
2. In the upper part of the screen, select the location
of the configuration you wish to restore. Then
select the required backup in the lower part of the
screen with the button.
If the configuration has been loaded from a USB
stick, you should additionally back it up in the
ETAtouch control system. To do this, perform the
backup again.