Checking outputs, changing terminal assignments Modify terminal assignment
Running direction of the heating circuit mixing
valve
1. With the [Service] authorization, open the inputs
and outputs menu in the heating circuit function
block. On the heating circuit mixing valve, tap the
symbol. The current status and position is
displayed.
2. The mixer can be opened and closed with the
[Forward] and [Back] buttons. Pressing the [Stop]
button keeps it in its current position.
3.3 Modify terminal assignment
Modify terminal assignment
The terminal assignment of the individual components
of the selected function block are displayed in the
inputs and outputs menu, e.g. pumps, temperature
sensors, and mixers. In this menu, the terminal
assignment can be changed.
In the example below, the terminal assignment of the
heating circuit pump is changed.
Modify terminal assignment of the heating circuit
pump
1. Increase the authorisation to [Service]. See
Chapter 3.1 "
Changing the access level".
2. Select the heating circuit and change the inputs
and outputs in the menu by tapping on the
symbol, followed by the symbol. The overview
screen opens.
Fig. 3-4: Overview
3. In the heating circuit pump, tap on the symbol.
The current terminal assignment is shown in the
upper area at [Current terminal assignment].
Fig. 3-5: Terminal allocation overview screen
The current allocation is erased with the button.
Next, select a free terminal from the [Available
terminals] list, and assign it using the button.
The changed allocation is displayed in the upper
area at [Current terminal assignment].