AT Product Lines
ATWB - Closed Circuit Cooler
ATC-E - Evaporative Condenser
eco-ATWB - Closed Circuit Cooler
eco-ATWB-E - Wet/Dry Closed Circuit Cooler
eco-ATWB-H - Wet/Dry Closed Circuit Cooler
eco-ATC-A - Wet/Dry Evaporative Condenser
eco-ATC-H Wet/Dry Evaporative Condenser
<
PHC - Parallel Hybrid Evaporative Condenser
Forced Dra
equipment includes the following Evapco Product Models:
<
LR Product Lines
LRWB - Closed Circuit Cooler
LRC - Evaporative Condenser
eco-LRWB - Wet/Dry Closed Circuit Cooler
<
LS Product Lines
LSWE - Closed Circuit Cooler
LSC-E - Evaporative Condenser
eco-LSWE - Wet/Dry Closed Circuit Cooler
<
PM Product lines
PMC-E - Evaporative Condenser
PMC-Q - Evaporative Condenser
eco-PMC - Wet/Dry Evaporative Condenser
If the unit will sit for idle periods of time it is recommended that the following be performed in addition to all component manufacturers
recommended maintenance instructions.
The fan/motor/pump bearings and motor bearings need to be turned by hand at least once a month. This can be accomplished
by tagging and locking out the unit’s disconnect, grasping the fan assembly (or removing the pump motor fan guard), and rotating it
several turns.
If unit sits longer than a few weeks, run gear reducer (if equipped) for 5 minutes weekly.
If unit sits longer than 3 weeks, completely fill gear reducer with oil. Drain to normal level prior to running.
If unit sits longer than one month, insulation test motor windings semi-annually.
If fan motor sits idle for at least 24 hours while the spray pumps are energized distributing water over the coil, motor space heaters
(if equipped) should be energized. Alternatively, fan motors may be energized for 10 minutes, twice daily, to drive any moisture
condensation out of the motor windings.
If coil sits longer than one month, nitrogen charge the coil.
Energize fan motors space heaters.
Initial Storage and/or Idle Period Recommendations

Table of Contents

Other manuals for EVAPCO ATC-E

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EVAPCO ATC-E and is the answer not in the manual?

EVAPCO ATC-E Specifications

General IconGeneral
BrandEVAPCO
ModelATC-E
CategoryAccessories
LanguageEnglish

Related product manuals