CHAPTER 4 Operating Instructions
4.1 Normal Mode
The UDACT-F has five modes of operation:
•Normal Mode
Type Mode
Program Mode
Lamp Test Mode
Troubleshoot Mode
Upon initial power-up, the system will be in Normal Mode. This section describes the operation of the UDACT-F in
the Normal Mode.
4.1.1 Keypad Functions
Clear
The Clear function will cause the UDACT-F to :
cease transmissions
clear any active or pending transmissions
reset and return to normal system processing
To perform the Clear function, press the CLEAR key followed by 2532 and then press the [ENTER/STORE] key.
2532 spells CLEA on a Touch-Tone
®
phone.
Te st
If the TEST key is pressed three times in rapid succession, the UDACT-F will transmit a test message to both Central
Stations. The message reported is the same as the automatic test message for all formats except Ademco Contact ID.
Mode
Pressing the MODE key followed by a valid 4-digit numerical code and pressing the [ENTER/STORE] key selects
one of the five modes of operation. To enter Normal Mode from any other mode, press the MODE key followed by
6676 and then the [ENTER/STORE] key.
6676 spells NORM on a Touch-Tone
®
phone.