Hot Water Series
5. Installation
5.1 Heat Pump unit Installation
1. The heat pump unit should be installed in a 9.The heat pump should be fixed firmly on the
ventilated place, with enough space for air inlet base. The bearing capability of the frame should
and outlet, while without thermal radiation or be as three times of weight as the heat pump
other heat source. Besides, the air outlet should unit. Reliable measures should be taken to keep
not be against the wind. the fastener stable. The unit base should be fixed
firmly by expansion bolts to ensure the entire
2. Generally, the vertical air flow type heat pump
unit stand erectly after installation.
does not need anything for sheltering. The
motor and other internal components have been 10. The unit location should avoid typhoon and
all waterproof. A shelter is required to avoid earthquake damage. The heat pump should not
snow burying onto the heat pump in heavily be installed in the air in case of crash accident.
snowy area.
11. The installation should be carried out
3. Please make sure the standardized voltage at the place of unobstructed ventilation of
220V or 380V is stably accessible to the heat the air outlet. (The inlet and outlet of the
pump, otherwise the performance would be air blower are illustrated in the following
influenced. diagram). The installation space should be
referred as follows:
4.The foundation of the heat pump can be
cement or steel structure. Anti-vibration rubber
and a flat foundation should be taken into
account. The foundation structure can be flexibly
designed according to the working weight of the
heat pump(Please see the technical data in this
manual.)
5. Water drainage should be available near the
installation location for draining water in an
effective way.
6.Do not install the heat pump in a place where
there is polluting or corrosive material like oil,
flammable and explosive gas and sulfide etc.
Keep it far away from sands, falling leaves and
area with high-frequency equipment.
7.The foundation should be heightened to avoid
the water inflow in rainy season and snow
burying in winter if it is installed in the open air.
8. Installation in balcony or on roof-top must be
accordance with the allowable stress of the
building structure.
Up flow
more than
2000mm
more than
1000mm
more than
1000mm
air inlet
air inlet
Horizontal View
enough space for
maintenance
more than
1000mm
more than
1000mm
more than
1000mm
air inlet
air inlet
air inlet
Vertical View
15