Limitation of data displayed on the LED monitor
Only four digits can be displayed on the 4-digit LED monitor. If you enter more than 4 digits of data
valid for a function code, any digits after the 4th digit of the set data will not be displayed; however
they will be processed correctly.
The following tables list the function codes available for the FVR-Micro inverters.
F codes: Fundamental Functions
Code Name Data setting range
Incre-
ment
Unit
F00
Data
Protection
0: Disable both data protection and digital reference
protection
1: Enable data protection and disable digital reference
protection
2: Disable data protection and enable digital reference
protection
3: Enable both data protection and digital reference
– – Y Y 0
F01
Frequency
Command 1
0: UP/DOWN keys on keypad
1: Voltage input to terminal [12] (0 to +10VDC)
2: Current input to terminal [C1] (4 to 20 mA DC)
3: Sum of voltage and current inputs to terminals [12]
and [C1]
4: Built-in potentiometer (POT)
7: Terminal command UP/DOWN control
– – N Y 4
F02
Operation
Method
0: RUN/STOP keys on keypad (Motor rotational
direction specified by terminal command FWD/REV)
1: Terminal command FWD or REV
2: RUN/STOP keys on keypad (forward)
3: RUN/STOP keys on keypad (reverse)
– – N Y 2
F03
Maximum
Frequency 1
25.0 to 400.0
0.1 Hz N Y 60.0
F04
Base
Frequency 1
25.0 to 400.0
0.1 Hz N Y 60.0
F05
Rated Voltage at
Base
Frequency 1
0: Output a voltage in proportion to input voltage
80 to 240: Output an AVR-controlled voltage (for 200 V
class series)
160 to 500: Output an AVR-controlled voltage (for 400
1 V N Y2
0
F06
Maximum Output
Voltage 1
80 to 240: Output an AVR-controlled voltage (for 200 V
class series)
160 to 500: Output an AVR-controlled voltage (for 400
1 V N Y2
220
(380)
F07
Acceleration Time 1
Note: Entering 0.00 cancels the acceleration time,
requiring external soft-start.
0.01 s Y Y 6.00
F08
Deceleration Time 1
Note: Entering 0.00 cancels the deceleration time,
requiring external soft-start.
0.01 s Y Y 6.00
F09
Torque Boost 1
0.0 to 20.0
(percentage with respect to "F05: Rated Voltage at
Base Frequency 1")
Note: This setting takes effect when F37 = 0, 1, 3, or 4.