3. Fan control
Tr: Room temperature
Ts: Setting temperature
3-1. Indoor fan control
¢ Fan speed
Indoor fan speed is defined as below.
Operation mode Fan mode
Speed (rpm)
ARXG36KMLA ARXG45KMLA
Heating
HIGH 1,270 1,300
MED 980 1,020
LO→ 790 840
QUIET 630 670
S-LO→ 420 420
Cooling
HIGH 1,130 1,310
MED 980 1,020
LO→ 790 840
QUIET 630 670
S-LO→ 420 420
Fan
HIGH 1,270 1,310
MED 980 1,020
LO→ 790 840
QUIET 630 670
Soft quiet 420 420
Dry
↓ zone: 630
J zone: 630
↓ zone: 670
J zone: 670
¢ Fan operation
Airflow can be switched in 5 steps such as AUTO, QUIET, LO→, MED, HIGH while indoor unit fan
only runs.
→hen fan mode is set at AUTO, it operates on MED fan speed.
¢ Cooling operation
Switch the airflow AUTO, and indoor fan motor will run according to room temperature, as below.
On the other hand, if switched in HIGH—QUIET, indoor motor will run at a constant airflow of COOL
operation modes QUIET, LO→, MED, HIGH as shown in “Fan speed” above.
Airflow change over (Cooling: Auto)
When room
temperature rises
When room
temperature drops
Tr - Ts ≥ 2°C
HIGH mode
MED mode
LOW mode
2
°C > Tr - Ts ≥ 1°C
1°C > Tr - Ts
Tr - Ts ≥ 2.5°C
2.5°C > Tr - Ts ≥ 1.5°C
1.5°C > Tr - Ts
3-1. Indoor fan control - (04-9) - 3. Fan control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS