2-5. E: 18. External communication error (Indoor unit)
Indicator
→ired remote
controller
Error code E: 18
Detective actuator Indoor unit
External
communication
error
After receiving a signal from the external input and
output PCB, the same signal has not been received for
15 seconds.
Forecast of cause
Connection failure
External input and output PCB failure
Main PCB
Check point 1. Check the connection
Check any loose or removed connection between the main PCB to the external input and out-
put PCB.
-> If there is an abnormal condition, correct it by refer to the installation manual or the “DESIGN
& TECHNICAL MANUAL”.
Check the connection condition on the external input and output PCB and the main PCB (If
there is loose connector, open cable or mis-wiring.)
Check point 2. Replace the external input and output PCB
If check point 1 do not improve the symptom, change external input and output PCB
Check point 3. Replace main PCB
If check point 2 do not improve the symptom, change main PCB
End
2-5. E: 18. External communication error (Indoor unit) - (03-10) - 2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING

Table of Contents

Other manuals for Fujitsu ARXG36KMLA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ARXG36KMLA and is the answer not in the manual?

Fujitsu ARXG36KMLA Specifications

General IconGeneral
BrandFujitsu
ModelARXG36KMLA
CategoryAir Conditioner
LanguageEnglish

Related product manuals