2. HEATING OPERATION
2-1 HEATING CAPACITY CONTROL
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive
difference or variation between a set temperature and present room temperature, and
controls the operation frequency of the compressor.
* If the room temperature is lower by 3°C than a set temperature, the compressor operation
frequency will attain to maximum performance.
* If the room temperature is higher 2.5°C than a set temperatire, the compressor will be
stopped.
minimum
frequency
maximum
frequency
ASYA07LCC 18Hz 130Hz
ASYA09LCC 18Hz
18Hz
130Hz
130Hz
ASYA12LCC
Outside air Outside air
temperature temperature
19°C
C zone
17°C
14°C
B zone
12°C
A zone
Hi Me Lo Quiet
A zone 130Hz 96Hz 80Hz 68Hz
B zone 130Hz 96Hz 80Hz 54Hz
07/09/12LCC
09/12LDC
C zone 130Hz 96Hz 80Hz 45Hz
* When the room temperature is between +2°C to -3°C of the setting temperature,
the compressor frequency is controlled within the range shown in Table2.
However, the maximum frequency is limited in the range shown in Figure 2 based on the
fan speed mode and the outdoor temperature.
( Table 2 : Compressor Frequency Range )
( Fig.2 : Limit of Maximum Frequency based on Outdoor Temperature )
* The room temperature is controlled 2°C higher than the setting temperature for 60 minutes
after starting the operation.
After 60 minutes, it is controlled based on the normal setting temperature.
05-02
ASYB09LDC 18Hz 130Hz
ASYB12LDC 18Hz
18Hz
130Hz
119Hz
ASYA14LCC
ASYA18LCC 18Hz 119Hz
A zone 119Hz 90Hz 70Hz 58Hz
B zone 119Hz 90Hz 70Hz 58Hz
14/18LCC
C zone 119Hz 90Hz 70Hz 58Hz