EasyManuals Logo
Home>Fujitsu>Air Conditioner>ASYG07KMCF

Fujitsu ASYG07KMCF User Manual

Fujitsu ASYG07KMCF
179 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #107 background imageLoading...
Page #107 background image
5-2. Inverter compressor
¢ Models: AOYG07KMCC, AOYG09KMCC, and AOYG12KMCC
Check point 1. Check connection
Check terminal connection of compressor (loose or incorrect wiring)
U(R)
(RED)
V(S)
(WHITE)
W(C)
(BLACK)
Main PCB
Check terminal connection of main PCB (loose or incorrect wiring)
Main PCB
W402(W)
Compressor
BLACK
WHITE
RED
W400(U)
W401(V)
Check point 2. Check winding resistance
Check winding resistance of each terminal.
Resistance value: 2.180 ±7% Ω at 20°C
U(R)
W(C)
V(S)
RED
WHITE
BLACK
→ If the resistance value is 0 Ω or infinite, replace compressor.
5-2. Inverter compressor - (03-65) - 5. Service parts information
TROUBLESHOOTING
TROUBLESHOOTING

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ASYG07KMCF and is the answer not in the manual?

Fujitsu ASYG07KMCF Specifications

General IconGeneral
BrandFujitsu
ModelASYG07KMCF
CategoryAir Conditioner
LanguageEnglish

Related product manuals