3. Fan control
Tr: Room temperature
Ts: Setting temperature
3-1. Indoor fan control
¢ Fan speed
Indoor fan speed is defined as below.
Operation mode Fan mode
Speed (rpm)
07 09 12 14
Heating
POWERFUL 1,230 1,270 1,310 1,400
HIGH 1,160 1,200 1,240 1,330
MED+ 1,060 1,060 1,120 1,160
MED 970 990 1,050 1,100
LOW 820 830 900 910
QUIET 650 650 650 670
Cool air prevention 570 570 570 580
S-LOW 420 420 420 470
Cooling/Fan
POWERFUL 1,140 1,200 1,200 1,320
HIGH 1,070 1,130 1,130 1,250
MED 920 940 940 1,020
LOW 780 780 780 810
QUIET 570 570 570 580
Soft quiet
490*
1
490*
1
490*
1
510*
1
S-LOW
420*
2
420*
2
420*
2
470*
2
Dry
X zone: 570
J zone: 570
X zone: 570
J zone: 570
X zone: 570
J zone: 570
X zone: 580
J zone: 580
*1: Fan mode only
*2: Cooling mode only
¢ Fan operation
Airflow can be switched in 5 steps such as AUTO, QUIET, LOW, MED, HIGH while indoor unit fan
only runs.
When fan mode is set at AUTO, it operates on MED fan speed.
3-1. Indoor fan control
- (04-10) - 3. Fan control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS