En-10
Room temperature sensor switching
(Onlyforwiredremotecontroller)
WhenusingtheWiredremotecontrollertemperaturesensor,changethesettingto“Both”(01).
(♦...Factorysetting)
Function
Number
Setting
Value
Setting Description
42
00 Indoorunit ♦
01 Both
00:Sensorontheindoorunitisactive.
01:Sensorsonbothindoorunitandwiredremotecontrollerareactive.
*
Remotecontrollersensormustbeturnedonbyusingtheremotecontroller.
Remote controller custom code
(Onlyforwirelessremotecontroller)
Theindoorunitcustomcodecanbechanged.Selecttheappropriatecustomcode.
(♦...Factorysetting)
Function
Number
Setting
Value
Setting Description
44
00 A ♦
01 B
02 C
03 D
External input control
“Operation/Stop”modeor“Forcedstop”modecanbeselected.
(♦...Factorysetting)
Function
Number
Setting
Value
Setting Description
46
00 Operation/Stopmode ♦
01 (Settingprohibited)
02 Forcedstopmode
Room temperature sensor switching (Aux.)
Tousethetemperaturesensoronthewiredremotecontrolleronly,changethesettingto“Wired
remotecontroller”(01).Thisfunctionwillonlyworkifthefunctionsetting42issetat“Both”(01)
(♦...Factorysetting)
Function
Number
Setting
Value
Setting Description
48
00 Both ♦
01 Wiredremotecontroller
Indoor unit fan control for energy saving for cooling
Enablesordisablesthepower-savingfunctionbycontrollingtheindoorunitfanrotationwhen
theoutdoorunitisstoppedduringcoolingoperation.
(♦...Factorysetting)
Function
Number
Setting
Value
Setting description
49
00 Disable
01 Enable ♦
00:Whentheoutdoorunitisstopped,theindoorunitfanoperatescontinuouslyfollowing
thesettingontheremotecontroller.
01:Whentheoutdoorunitisstopped,theindoorunitfanoperatesintermittentlyatavery
lowspeed.
Setting record
Recordanychangestothesettingsinthefollowingtable.
Setting Description Setting Value
Filtersign
Roomtemperaturesensorcontrolforcooling
Roomtemperaturesensorcontrolforheating
Autorestart
Roomtemperaturesensorswitching
Remotecontrollercustomcode
Externalinputcontrol
Roomtemperaturesensorswitching(Aux.)
Indoorunitfancontrolforenergysavingforcooling
AftercompletingtheFunction Setting,besure todisconnectthe powersupplyand then
reconnectit.
13. TEST RUN
Check items
(1) Isoperationofeachbuttonontheremotecontrollernormal?
(2) Doeseachlamplightnormally?
(3) Doairowdirectionlouversoperatenormally?
(4) Isthedrainnormal?
(5) Donothaveanabnormalnoiseandvibrationduringoperation?
•
Donotoperatetheairconditionerintestrunforalongtime.
[Operation method]
•
Fortheoperationmethod,refertotheoperatingmanual.
•
Theoutdoorunit,maynotoperate,dependingontheroomtemperature.Inthis
case,keeponpressingtheMANUALAUTObuttonoftheindoorunitformorethan
10seconds.Theoperationindicatorlampandtimerindicatorlampwillbegintoash
simultaneouslyduringcoolingtestrun.Then,heatingtestrunwillbegininaboutthree
minuteswhenHEATisselectedbytheremotecontroloperation.(Pleasefollowthe
operatingmanualforremotecontroloperation.)
•
Toendtestoperation,presstheremotecontrollerSTART/STOPbutton.
(Whentheairconditionerisrunningbypressingthetestrunbutton,theOPERATION
LampandTIMERLampwillsimultaneouslyashslowly.)
[Using the wired remote controller] (Option)
Fortheoperationmethod,refertotheoperatingmanual.
(1) Stoptheairconditioneroperation.
(2) Pressthemastercontrolbuttonandthefancontrolbuttonsimultaneouslyfor2
secondsormoretostartthetestrun.
Testrundisplay
(3) Pressthestart/stopbuttontostopthetestrun.
14. CUSTOMER GUIDANCE
Explainthefollowingtothecustomerinaccordancewiththeoperatingmanual:
(1)Startingandstoppingmethod,operationswitching,temperatureadjustment,timer,air-
owswitching,andotherremotecontrolleroperations.
(2)Airlterremovalandcleaning,andhowtousetheairlouvers.
(3)Givetheoperatingmanualtothecustomer.