3-2. Outdoor fan control
¢ Outdoor fan motor
This outdoor unit has a DC fan motor. (Control method is different between AC and DC motors.)
¢ Fan speed
 Model: AOHG30KBTA4
Fan speed is defined by outdoor temperature and compressor frequency.
Unit: rpm
Fan step Cooling or dry Heating
S-HIGH — 1,200
13 1,150 —
12 1,150 —
11 1,150 —
10 1,080 1,200
9 920 1,110
8 860 1,030
7 770 990
6 680 860
5 630 800
4 560 700
3 490 640
2 390 600
1 270 550
• When the compressor frequency increases, the outdoor fan speed also changes to the higher
speed.
• When the compressor frequency decreases, the outdoor fan speed also changes to the lower
speed.
NOTE: After defrost control on the heating mode, the fan speed is kept higher regardless of the
compressor frequency.
Fan speed after defrost control: 1,200 rpm
3-2. Outdoor fan control - (04-53) - 3. Fan control