2-2. Outdoor unit low noise operation function (option)
Change the outdoor unit low noise operation by using this setting.
CAUTION
When the low noise operation function is working, cooling and heating capacity will de-
crease.
When changing the settings, explain to the customer beforehand that the capacity decreas-
es.
NOTES:
When SET1-4 is OFF, optional Central remote controller is required to use this function.
When SET1-4 is ON, “Operation” and “Non-operation” mode of this function cannot be
switched from the Central remote controller.
SET1-4 Setting Factory setting
ON Continuous operation
OFF
Follow the Central remote controller
settings
SET2-1 Setting Factory setting
ON Lower
OFF Low
2-3. Changing the current limit function
Change the outdoor unit current limit function by using this setting.
CAUTION
When the current limited function is working, cooling and heating capacity will decrease.
When changing the settings, explain to the customer beforehand that the capacity decreases.
SET2-3 SET2-4 Current Factory setting
OFF OFF Full
ON OFF 16.0 A
OFF ON 12.0 A
2-2. Outdoor unit low noise operation function (option) - (05-55) - 2. Function settings (for outdoor unit)
FIELD
WORKING
FIELD
WORKING

Table of Contents

Other manuals for Fujitsu AUXG07KVLA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AUXG07KVLA and is the answer not in the manual?

Fujitsu AUXG07KVLA Specifications

General IconGeneral
BrandFujitsu
ModelAUXG07KVLA
CategoryAir Conditioner
LanguageEnglish

Related product manuals