2-35. E: 94. Trip detection (Outdoor unit)
Indicator Indoor unit
Operation indicator 9 time flash
Timer indicator 4 time flash
Economy indicator Continuous flash
Error code E: 94
Detective actuator Outdoor unit
Main PCB Protection stop by over-current generation after inverter
compressor start processing completed generated
consecutively 10 times.
NOTE: The number of generations is reset when the
compressor starts up.
Compressor
Forecast of cause
Outdoor unit fan operation defective, foreign matter on
heat-exchanger, excessive rise of ambient temperature
Main PCB failure
Inverter compressor failure (lock, winding short)
Check point 1. Check the outdoor unit fan operation, heat-exchanger, ambient temperature
• No obstructions in air passages?
• Heat exchange fins clogged
• Outdoor unit fan motor check
• Ambient temperature not raised by the effect of other heat sources?
• Discharged air not sucked in?
↓
Check point 2. Replace the main PCB
If Check point 1 do not improve the symptom, replace the main PCB.
↓
Check point 3. Replace compressor
If Check point 2 do not improve the symptom, change compressor.
↓
End
2-35. E: 94. Trip detection (Outdoor unit) - (03-48) - 2. Troubleshooting with error code