10. Electrical characteristics
Model name AOHG36KRTA
Power
supply
Voltage V 3N 400 ~
Frequency Hz 50
Max operating current *1 A 10.5
Starting current A 5.5
Wiring
spec. *2
Circuit breaker current A 16
Power cable
mm
2
2.5
Connection
cable *3
Cross-sectional area
mm
2
1.5
Limited wiring length m 51
Model name AOHG45KRTA AOHG54KRTA
Power
supply
Voltage V 3N 400 ~
Frequency Hz 50
Max operating current *1 A 14.0
Starting current A 6.6 8.0
Wiring
spec. *2
Circuit breaker current A 16
Power cable
mm
2
2.5
Connection
cable *3
Cross-sectional area
mm
2
1.5
Limited wiring length m 51
*1: Maximum current is the total current of the indoor unit and the outdoor unit.
*2: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005. As
the regulations of wire size and circuit breaker differ in each country or region, select appropriate de-
vices complied to the regional standard.
*3: Limit voltage drop to less than 2%. Increase conductor size if voltage drop is 2% or more.
- 59 -
10. Electrical characteristics
OUTDOOR UNIT
AOHG36-54KRTA
OUTDOOR UNIT
AOHG36-54KRTA

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu General ARXG36KHTAP and is the answer not in the manual?

Fujitsu General ARXG36KHTAP Specifications

General IconGeneral
BrandFujitsu
ModelGeneral ARXG36KHTAP
CategoryAir Conditioner
LanguageEnglish

Related product manuals