EasyManuals Logo
Home>GE>Relays>Agile P50 Series

GE Agile P50 Series User Manual

GE Agile P50 Series
268 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #210 background imageLoading...
Page #210 background image
12 SCADA Communications
P50 Agile P153
9-4
2 SCADA COMMUNICATIONS
2.1 Modbus
This section describes how the MODBUS standard is applied to the Px50 platform. It is not a
description of the standard itself. The level at which this section is written assumes that the reader is
already familiar with the MODBUS standard.
The MODBUS protocol is a master/slave protocol, defined and administered by the MODBUS
Organization. For further information on MODBUS and the protocol specifications please see the
Modbus web site (www.modbus.org).
2.1.1 Overview
2.1.1.1 Physical Connection and Link Layer
Only one option is available for connecting MODBUS.
Rear serial port 1 - for permanent SCADA connection via EIA(RS)485
The MODBUS interface uses ‘RTU’ mode communication rather than ‘ASCII’ mode as this provides
more efficient use of the communication bandwidth. This mode of communication is defined by the
MODBUS standard.
The IED address and baud rate can be selected using the front panel menu or with P50 Agile
configurator.
When using a serial interface, the data format is: 1 start bit, 8 data bits, 1 stop bit (a total of 10 bits per
character).
2.1.2 MODBUS Functions
2.1.2.1 Protocol Mapping
The following MODBUS function codes are supported:
Code
Function Name
Addresses starts with
02 Read Input Status 1x addresses
03 Read Holding Registers 4x addresses
04 Read Input Registers 3x addresses
05 Force Single Coil 0x addresses
16 Preset Multiple Registers 4x addresses
Exception Codes generated in case of an error:
Code MODBUS Response Name Product interpretation
01 Illegal Function Code The function code received in query is not supported by the IED.
02 Illegal Data Address The start address received in the query is not an allowable value.
Note: If the start address received is correct but
the range includes unsupported address,
then this error is produced.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Agile P50 Series and is the answer not in the manual?

GE Agile P50 Series Specifications

General IconGeneral
BrandGE
ModelAgile P50 Series
CategoryRelays
LanguageEnglish

Related product manuals