EasyManuals Logo
Home>GE>Relays>Agile P50 Series

GE Agile P50 Series User Manual

GE Agile P50 Series
268 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #239 background imageLoading...
Page #239 background image
P50 Agile P153
13 Commissioning Instructions
P153/EN M/B
13-7
2. Apply a current of twice the setting shown in the I>1 Current Set cell in the OVERCURRENT
menu.
3. Note the time displayed when the timer stops.
4. Check that the red trip LED has illuminated.
2.1.11.4 Checking the Operating time
Check that the operating time recorded by the timer is within the range shown below.
For all characteristics, allowance must be made for the accuracy of the test equipment being used.
Characteristic
Operating time at twice current setting and time multiplier/
time dial setting of 1.0
Nominal (seconds)
Range (seconds)
DT I>1 Time Delay setting
Setting ±5% or 55ms whichever is greater*
(*Fault current 2 times the set value)
IEC S Inverse 10.03
Please refer to the Technical Specifications
chapter for operating time accuracy
IEC V Inverse
13.50
IEC E Inverse
26.67
UK LT Inverse 20.00
IEEE M Inverse 3.8
IEEE V Inverse 7.03
IEEE E Inverse
9.50
US Inverse
2.16
US ST Inverse 12.12
Note: With the exception of the definite time characteristic, the operating times given are for a Time
Multiplier Setting (TMS) or Time Dial Setting (TDS) of 1. For other values of TMS or TDS, the values
need to be modified accordingly
Caution: On completion of the tests, you must restore all settings that were
disabled
2.1.12 Onload checks
Onload checks can only be carried out if there are no restrictions preventing the energisation of the
plant, and the other devices in the group have already been commissioned.
Remove all test leads and temporary shorting links, then replace any external wiring that has been
removed to allow testing.
Caution: If any external wiring has been disconnected for the commissioning
process, replace it in accordance with the relevant external
connection or scheme diagram.
2.1.12.1 Onload checks
1. Measure the current transformer secondary values for each input using a multimeter
connected in series with the corresponding current input.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Agile P50 Series and is the answer not in the manual?

GE Agile P50 Series Specifications

General IconGeneral
BrandGE
ModelAgile P50 Series
CategoryRelays
LanguageEnglish

Related product manuals